FENWAL CONTROLS Ignition Control Module, Series: 05-32, 24 VAC, 6100 mA Ignition, 80 mA Running, 50/60 Hz
Amperage Rating |
: |
6100 mA Ignition, 80 mA Running |
Frequency Rating |
: |
50/60 Hz |
Series |
: |
05-32 |
Voltage Rating |
: |
24 VAC |
- Compact units having a nominal igniter warm-up period 45 sec
- If after a try-for-ignition, a flame is not present, the unit goes into lockout de-energizing the gas valve automatically
- Resetting after the lockout is accomplished by cycling the wall thermostat down to its lowest setting then back to the desired comfort setting
- If the flame is lost during normal heat cycle, a new trial for ignition sequence will commence
- Nominal current drain - 80 mA maximum (running), 6100 mA maximum (during ignition)
- 2 A maximum at 24 VAC gas valve relay rating
- 5 A maximum at 24 VAC igniter relay rating
-
Specification Sheet
https://assets.unilogcorp.com/267/ITEM/DOC/Fenwal_Controls_05_326225_053_Specification_Sheet.pdf