The Single Duct Air Terminal Zone Controller provides dedicated control functions for single duct terminals with modulating heat or up to 2-stages of heat. The zone controller is part of the Carrier® ComfortID™ System.
Carrier® ComfortID™ Zone Controller, 24 VAC, VA Rating: 40 VA, 50/60 Hz, 0 to 90 % Humidity Rating, 2 Stages, Single Duct Air Terminal, 22 to 18 AWG Wire, 32 to 140 deg F, 9 in L x 5 in W x 3 in H
Dimensions |
: |
9 in L x 5 in W x 3 in H |
Frequency Rating |
: |
50/60 Hz |
Humidity Rating |
: |
0 to 90 % |
Stages |
: |
2 |
Temperature Rating |
: |
32 to 140 deg F |
Terminal Type |
: |
Single Duct Air |
VA Rating |
: |
40 VA |
Voltage Rating |
: |
24 VAC |
Wire Size |
: |
22 to 18 AWG |
- Provides pressure independent (VAV) control
- Uses proportional integral derivative (PID) control
- Mounts directly onto VAV box damper shaft
- Terminal fan control
- For terminals up to 9000 cfm or 3.4 sq-ft inlet (primary air)
- Auxiliary heating control of modulating (floating) hot water, single-position hot water, single or two-stage electric or zone perimeter heat
- Quick and easy commissioning and balancing process
- Automatic self-calibration of airflow transducer
- Capable of stand-alone operation with supply air temperature sensor
- Actuator preassembled to housing
- Capable of demand controlled ventilation support with field installed IAQ sensor
- Easy access to airflow sensor pneumatic connections
- Uses Carrier® Comfort™ network (CCN) protocol
- Capable of high-speed 38.4 k baud communications network operation
- 128 controller maximum system (must be located on same CCN bus segment)
-
Catalog
https://assets.unilogcorp.com/267/ITEM/DOC/Carrier_33ZCFANTRM_Catalog.pdf
-
Instruction/Installation Manual
https://assets.unilogcorp.com/267/ITEM/DOC/Carrier_33ZCFANTRM_Instruction_Installation_Manual.pdf
-
Specification Sheet
https://assets.unilogcorp.com/267/ITEM/DOC/Carrier_33ZCVAVTRM_Specification_Sheet.pdf