Rheem® Duct Smoke Detector, Series: SL-2000-P, Photoelectric, Red LED Visual Indicator Type, 85 +/-5% RH at 32 +/-2 deg C Non-Condensing/Non-Freezing Humidity, LED, Solid/Stranded Wire, 18 mA at 230 VAC, 32 mA at 115 VAC, 190 mA at 24 VAC, 68 mA at 24 VDC Alarm Current, Clear Cover, 32 to 140 deg F
Alarm Current
:
18 mA at 230 VAC, 32 mA at 115 VAC, 190 mA at 24 VAC, 68 mA at 24 VDC
Color
:
Clear Cover
Detection Method
:
Photoelectric
Display Type
:
LED
Humidity Rating
:
85 +/-5% RH at 32 +/-2 deg C Non-Condensing/Non-Freezing
Series
:
SL-2000-P
Temperature Rating
:
32 to 140 deg F
Visual Indicator Type
:
Red LED
Wire Type
:
Solid/Stranded
Low flow technology: both ionization and photoelectric models listed for velocities between 100-4000 fpm
Both models listed for high temperature applications
Patent pending "no-tools required" front or rear loading and removing sampling/exhaust tubes
Patent pending "test port valve" allows for aerosol smoke testing without cover removal
Clear cover fitted with (4) Captive "No-Tools Required" thumbscrews
Staggered terminal blocks for easier wiring
Flashing LED on detector head indicates normal operation
Magnet test capability (magnet included)
More wiring space than competitive models
Duct wall gaskets on back of enclosure are pre-installed
Compatible with the WP-2000 Weather-proof enclosure
Reset switch is also an alarm test switch-competitive models require a magnet or cover removal to test at unit
Unit includes green pilot and red alarm visual indicators
External mounting tabs do not require cover removal to install
Colored cover gasket indicates proper cover seal
Compact, lightweight size means easy handling, lower shipping costs
(2) sets of 10A form "C" alarm contacts (1) set of 2A form "A" alarm contacts (1) set of 10A form "C" trouble contacts, large terminal connection screws
Standard interchangeable plug-in UL268 photoelectric or ionization heads